Frequently Asked Questions
Q. "How much can I expect my water pressure to fluctuate after I install the constant water pressure system?"
A. The Constant Pressure System's constant output pressure should not fluctuate more than 1-2 PSI, even though the overall system's water flow requirement may change dramatically.
Q. "What is the incoming pressure requirement for these units?"
A. The Versaboost Pro constant pressure system requires a minimum of 20 psi if used with a utility or well pump. If you have a water storage tank or cistern, then you will need 1-19 psi if the water storage tank is installed above the booster. If your water storage tank is installed below the booster, then you need less than 1 psi.
Q. "What is the water flow requirement for the constant pressure unit?"
A. The system operates on a wide range of flows from flooded suction to 19 GPM at 14 PSI maximum. The Versaboost Pro can lift water from a source below the pumping unit upto 25 feet. There is not an incoming flow requirement, other than the system needs to be supplied with a constant supply of water to keep the unit completely full of water at all times with a maximum flow of 18 gpm. It is recommended that the system be supplied with inlet line that is 3/4" in diameter or larger. Please note although the unit has no water flow requirement other than being kept full at all times, you still must meet the minimum water pressure requirement of 1 PSI.
Q. "What is the difference between water flow and water pressure?"
A. Water flow refers to the amount of water coming out of a hose, faucet or other pipe fixture in a certain amount of time. Water pressure refers to the amount of force that is put on the water to make it move from one place to another, or to the amount of force the water exerts when coming out of the pipe. Water flow is the result of pressure on volume. Volume is the amount of water available for delivery, and pressure is the force exerted on it. For example if you have a pressure of 3 PSI forcing water through a 1/2" i.d. pipe it will have a lower flow rate than that same 3 PSI forcing water through a larger pipe.
Q. "What does flooded suction mean?"
A. A "flooded suction" refers to a situation in where water flows to the pump inlet from an elevated source by means of gravity.
Q. "My water is sandy and somewhat abrasive. Can I still use these systems?"
A. Pumping abrasive or sandy water can damage any pump's internal components. We suggest installing a sand separator before the constant pressure or boosting system if you have these water conditions. We have many sand separators for you to choose from. Please note: If you are considering adding a sand separator before the constant water system you must make sure that your water system meets the minimum flow rate for the sand separator to function correctly.
Q. "Will I experience water hammer while using the constant pressure system?"
A. The pressure tank helps reduce water hammer by acting as a system buffer. However you may still need a water hammer arrester as water hammer is caused by a rapid shut off of a valve on a long run at the end of your plumbing system and the constant pressure system is installed at the beginning of your plumbing system.
Q. "What other items and/or tools will be needed to install the constant pressure system?"
A. The manufacturer recommends but does not include: wrenches, screwdriver, pipe sealant, pipe fittings, nipples, check valves, ball valves, unions and a 100 PSI pressure relief valve.
Q. "Can the pump run dry without any damage?"
A. No, never run the pump dry.
Q. "Will this system be able to handle other liquids besides water?"
A. Per the manufacturer, this pump has been evaluated for use with water only.
Q. "What is NEMA3R rating mean?"
A. The NEMA3R rating means that the units enclosure provides a degree of protection from outdoor environmental factors like rain, sleet, and snow. It will not protect against dust or dirt. For indoor use this inclosure protects against accidental contact with live components, falling dirt, and light water splashing. The unit can be installed outdoors but the manufacturer recommends that the unit be shielded from direct sunlight to prevent overheating.